Table 430-148

(From 1999 NEC)

Full-Load Currents in Amperes, Single-Phase Alternating-Current Motors

The following values of full-load currents are for motors running at usual speeds and motors with normal torque characteristics. Motors built for especially low speeds or high torques may have higher full-load currents, and multi-speed motors will have full-load current varying with speed, in which case the nameplate current ratings shall be used.

The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120 and 220 to 240 volts.

Horsepower 115 Volts 200 Volts 208 Volts 230 Volts
1/6 4.4 2.5 2.4 2.2
1/4 5.8 3.3 3.2 2.9
1/3 7.2 4.1 4.0 3.6
½ 9.8 5.6 5.4 4.9
¾ 13.8 7.9 7.6 6.9
1 16 9.2 8.8 8.0
20 11.5 11.0 10
2 24 13.8 13.2 12
3 34 19.6 18.7 17
5 56 32.2 30.8 28
80 46.0 44.0 40
10 100 57.5 55.0 50